Overview

Efficient overhead distribution for every service territory

We supply single-phase pole-mounted transformers that reduce the length of low-voltage distribution lines, lower line losses and improve power-supply quality. A highly efficient, energy-saving wound-core design gives small size, low infrastructure investment, a reduced low-voltage supply radius and low-voltage line losses cut by over 60%.

A fully sealed structure provides strong overload capacity, high reliability in continuous operation and simple maintenance — ideal for rural networks, remote terrain and grid energy-saving renovations.

DOE 2016CSA 2023Fully sealed
Single-phase pole-mounted transformers on a light background
Specifications

Single-Phase Pole-Mounted Transformer

Single-Phase Pole-Mounted — Ratings & Efficiency
Rated capacity5, 10, 15, 25, 37.5, 50, 75, 100, 167 kVA
High voltage (HV)12.47/7.20, 13.2/7.62, 13.8/7.96, 34.5/19.92 kV (or as specified)
Low voltage (LV)120/240, 240/480, 347, 600 V
Efficiency — DOE (2016)98.58% (5 kVA) up to 99.33% (167 kVA)
Efficiency — CSA (2023)98.47% up to 99.28%
TypeFully sealed, oil-immersed, self-cooled
StandardsANSI/IEEE & IEC; DOE 2016 / CSA 2023 efficiency

Indicative ranges from the manufacturer's selection guide. Final ratings, taps, impedance and accessories are configured to your project specification.

Why this design

Engineered to last in the field

Small size & low cost

Compact wound-core construction lowers infrastructure investment and the low-voltage supply radius.

Fully sealed

Sealed structure keeps oil isolated from air for a long, dependable service life.

Strong overload capacity

Handles the demand swings of rural and agricultural loads without derating.

High reliability

Built for continuous operation with high reliability and simple, infrequent maintenance.

Energy-saving core

Efficient coil-core design cuts low-voltage line losses by more than 60%.

Simple maintenance

Field-friendly design for fast inspection and service on the line.

Applications

Where these transformers fit

Rural power gridsRemote & mountainous areasScattered villagesLine extensionsAgricultural loadsLighting circuitsRailway grid upgradesUrban grid energy-saving renovations

Need pole-mounted units for a US or Canadian project?

Send your kVA, voltages, taps and accessory schedule — we'll return an engineered quote with drawings and a DOE/CSA efficiency statement.